Flooring Guides · Heated Floors

How to Install Heated Floors Under Tile: Schluter DITRA-HEAT Explained

How heated tile floors are installed with Schluter DITRA-HEAT: planning the heated area, the electrician's rough-in, bonding the membrane, laying and testing the cable, the floor sensor, tiling, floor height and DITRA-HEAT-DUO for concrete.

Orange Schluter-DITRA membrane on a floor with plank-style porcelain tile being installed over it with levelling clips
Plank tile going down over a Schluter-DITRA membrane, installed by Agora Flooring.

Short answer

DITRA-HEAT is Schluter's uncoupling membrane with a pattern of studs that hold an electric heating cable. To install heated floors with it, the membrane is bonded to the subfloor, the cable is pressed between the studs where you want heat, a floor sensor goes in between two cable runs, and tile is set directly on top. The cable is tested before, during and after tiling, and a thermostat wired by a licensed electrician controls it. DITRA-HEAT-DUO adds a thin fleece underneath that acts as a thermal break, which suits concrete slabs and basements.

Heated floors are one of the most-requested upgrades in Ottawa bathrooms. Cold tile in January is a big part of why, and DITRA-HEAT is one of the most common systems for it. Here is how to install in-floor heating under a heated tile floor, step by step, and what to decide before installation day.

Putting in heated floors is mostly a tile job with an electrical job on each side of it. The electrician prepares the circuit and the thermostat box before the floor goes down and makes the final connection after the tile has cured. In between, the tile installer prepares the subfloor, installs the membrane, lays the cable and sensor, tests the cable and sets the tile. The steps have to happen in that order, which is why heat is planned at the start of a renovation, not added once the tile is ordered.

What DITRA-HEAT does

  • Heats the floor: the cable sits just under the tile, so the floor warms up relatively quickly.
  • Uncouples the tile: like regular DITRA, it lets the subfloor move slightly without cracking the tile (see what DITRA does).
  • Waterproofs: with the seams sealed with KERDI-BAND, it forms a waterproof layer over the floor.
  • Flexible layout: the cable can be placed only where you'll stand, kept out from under the vanity and toilet, and run closer near cold exterior walls within the maker's limits.

Those four jobs are the reason a cable-in-membrane system is the usual choice under tile. A heating mat needs its own layer of thin-set or self-levelling compound over it before the tile, and an uncoupling membrane would be a separate layer again. With DITRA-HEAT, the studs hold the cable and the tile is set straight onto the membrane, with no self-levelling compound needed to cover the cable.

DITRA-HEAT vs DITRA-HEAT-DUO

DITRA-HEAT-DUO is the same membrane with a thin fleece bonded underneath. The fleece slows heat loss into the floor below, so a cold slab warms up faster, and it also reduces impact sound. It is the usual choice over concrete, in basements and in condos. Both versions add a little height (DUO slightly more), so plan transitions to neighbouring floors.

How thick is it? The thinnest floor heating systems for tile

Floor height is one of the first questions in any heated floor, because the new floor has to meet the hallway, clear the door and still let the toilet seal and the dishwasher slide in. The standard DITRA-HEAT membrane is a nominal 1/4" (5.5 mm) thick, and DITRA-HEAT-DUO is a nominal 5/16" (8 mm), as Schluter lists them. On top of that come the thin-set and the tile. Because the cable sits inside the membrane's studs, there is no extra layer of self-levelling compound over it, which keeps the build-up low.

The thinnest floor heating systems overall are heating films, but they are made for floating floors such as laminate, not for tile. Under tile, a heating mat covered with thin-set can also be thin, but a mat set in self-levelling compound adds the depth of that pour. Whatever the system, the finished height is worked out before anything is ordered: subfloor, membrane, mortar and tile added together, compared with the floors next door.

How to install heated floors under tile, step by step

1. Plan the heated area

Measure the open floor where people walk, leaving out spaces under cabinets, the vanity, the tub and the toilet, kept back from the toilet flange by the distance the maker specifies. Cable comes in fixed lengths and cannot be cut, so the length is chosen to fit the area. That means the fixtures have to be chosen and placed first. A quick drawing of the floor with the fixtures, the door and the thermostat location is the plan everyone works from.

2. Electrical rough-in

A dedicated circuit and a box for the thermostat. In Ontario, electrical work needs an ESA permit and is done by a licensed electrical contractor (or a homeowner under their own permit). The thermostat box goes outside the wet area, usually near the door, with a path for the cable's power lead and the sensor wire to reach it from the floor. If the walls are open, this is the easy time to do it.

3. Prepare the subfloor

It must be solid and flat. Wood subfloors must be stiff enough for tile. Low spots get patched or levelled first (see self-leveling compound). The surface is cleaned of dust, old adhesive and anything else that would stop the mortar bonding, and any screws or nail heads are set flush so they can't damage the membrane or the cable.

4. Bond the membrane

Thin-set is spread with the trowel Schluter specifies, and the membrane is pressed in and rolled for full contact. Sheets are butted together, not overlapped. Where the floor has to be waterproof, the seams and the joints at the walls are covered with KERDI-BAND, as the handbook shows.

5. Test the cable

Its resistance is measured with an ohmmeter out of the box, after installing it and after tiling, and recorded for the warranty. Each reading is compared with the range on the cable's label. A reading outside that range before tiling means the cable is fixed or replaced while it is still easy to reach.

6. Install the cable

It is pressed between the studs at the spacing Schluter specifies (typically every third stud) and never crossed, overlapped or cut. The cable runs back and forth across the heated area, kept the specified distance from walls and fixtures, and the factory splice between the heating cable and the power lead sits in the floor, embedded in mortar, as the instructions require.

7. Place the floor sensor

The sensor goes between two cable runs, and its wire is led to the thermostat box. Many installers lay a spare, because a sensor can't be replaced once it's tiled over.

8. Tile

Thin-set fills the membrane cavities and the tile is set as on any DITRA floor, using a mortar Schluter approves. The trowel and the coverage are the same as for any floor tile, with full support under every tile so nothing sounds hollow. Spacers, levelling clips and cuts are handled carefully so nothing pierces the cable, and the cable is tested again once the tile is down.

9. Connect and wait

The electrician connects the thermostat. The heat stays off until the mortar has fully cured. Then the thermostat is set to a schedule, and the readings, the warranty registration and the thermostat manual are kept together.

Installing floor heating in a renovation: the order of trades

In a bathroom renovation, a heated floor slots into a sequence. The old floor comes out, the plumber roughs in the drain and supply lines, and the electrician roughs in the circuit and the thermostat box. The subfloor is then checked, repaired and levelled, and the membrane, cable and sensor go in. The tile goes down, the cable is tested again, and the floor is grouted. Once the mortar and grout have cured, the electrician makes the final connection and the plumber sets the toilet and vanity. Getting that order right is what keeps a heated floor from being damaged by a later trade, and it is why we plan the heated area with you before the tile is ordered.

Thermostats

Schluter's DITRA-HEAT thermostats include ground-fault protection, which heated floors in bathrooms need. Programmable and Wi-Fi models let the floor warm up before you wake and switch off when you're out. A schedule makes a big difference to running cost (see are heated floors worth it?).

Can heated floors go under vinyl or laminate?

DITRA-HEAT is designed for tile and stone. Some luxury vinyl and laminate products allow certain heating systems underneath, with limits on floor temperature. Check the flooring maker's instructions before planning heat under anything other than tile.

Mistakes to avoid

  • Cable under the toilet or vanity, where the heat is trapped.
  • Skipping the resistance tests, which makes a damaged cable hard to prove or find.
  • Turning the heat on early to "dry" the thin-set.
  • Not planning for the added floor height at doors and transitions.

Most of these come from rushing the planning. Ordering the cable before the vanity and toilet are chosen leads to cable under fixtures or a length that doesn't fit. Leaving the thermostat location to the end leads to a sensor wire that won't reach. A heated floor is quick to install once it is planned, and slow and costly to fix once it is tiled over.

Can you install heated floors yourself?

If you are working out how to put in heated floors yourself: a homeowner can install the membrane and cable, and in Ontario can do their own electrical work under their own ESA permit. In practice, the cable is the part that is easy to damage and hard to fix once it is under tile, so the planning, the testing at every stage and the tile setting over it all need care. If you are tiling the floor yourself, follow the system's installation handbook exactly, keep the test readings, and have the connection done by a licensed electrician if you are not taking out your own permit. If you would rather have it done for you, our heated floor installation page explains how we plan and install it with the tile.

Frequently asked questions

How do you install heated floors under tile?

Plan the heated area around the fixtures, have the electrician rough in a circuit and thermostat box, prepare a flat, solid subfloor, bond the heating membrane, press in the cable and the floor sensor, test the cable, then tile with a mortar the system's maker approves. The electrician connects the thermostat, and the heat stays off until the mortar has cured.

What is the thinnest floor heating system for tile?

Under tile, a cable-in-membrane system keeps the build-up low because no self-levelling layer is needed over the cable. Schluter lists DITRA-HEAT at a nominal 1/4" (5.5 mm) and DITRA-HEAT-DUO at 5/16" (8 mm), before mortar and tile. Heating films are thinner but are made for floating floors, not tile.

Can you cut DITRA-HEAT cable to fit the room?

No. The heating cable comes in fixed lengths and must never be cut, crossed or overlapped. The heated area is measured first, leaving out the spaces under the vanity, tub, toilet and cabinets, and a cable length is chosen to fit that area.

How long after tiling can you turn on a heated floor?

Not until the mortar has fully cured, following the mortar maker's cure times. Turning the heat on early to dry the thin-set is a common mistake that can weaken the bond under the tile. The electrician can connect the thermostat, but the heat stays off until then.

Do I need an electrician for DITRA-HEAT in Ontario?

Yes. In Ontario, the electrical work needs an ESA permit and is done by a licensed electrical contractor, or by a homeowner under their own permit. That covers the dedicated circuit, the thermostat box and the final connection, while the tile installer places the membrane, cable and sensor.

Is DITRA-HEAT-DUO better over a concrete slab?

Usually, yes. DUO has a thin fleece under the membrane that acts as a thermal break, so less heat is lost into a cold slab and the floor warms faster. It also reduces impact sound, which is why it is the usual choice in basements and condos.

Why is the heating cable tested during installation?

To prove it wasn't damaged. Its resistance is measured with an ohmmeter out of the box, after it is installed and again after tiling, and the readings are recorded for the warranty. Without those tests, a damaged cable is hard to prove or find.